Table of Contents
Short User Guide for the Cisco cBR Series Converged Broadband Routers
Installation Warning Statements
Attaching the Installation Handle (optional)
Installing the Cable-Management Brackets
Attaching a Chassis Ground Connection
Installing the Power System in the Cisco cBR Chassis
Installing the Power Cassette Module in the Cisco cBR Chassis
Installing the FPEM in the Cisco cBR Chassis
Installing the Power Module in the Cisco cBR Chassis
Connecting Power to the AC-Powered Cisco cBR Chassis
Connecting Power to the DC-Powered Cisco cBR Chassis
Conventions
This document uses the following conventions:
Note Means reader take note. Notes contain helpful suggestions or references to material not covered in the manual.
Caution Means reader be careful. In this situation, you might perform an action that could result in equipment damage or loss of data.
Warning IMPORTANT SAFETY INSTRUCTIONS
This warning symbol means danger. You are in a situation that could cause bodily injury. Before you work on any equipment, be aware of the hazards involved with electrical circuitry and be familiar with standard practices for preventing accidents. Use the statement number provided at the end of each warning to locate its translation in the translated safety warnings that accompanied this device.
SAVE THESE INSTRUCTIONS
Product Description
The Cisco cBR Series Converged Broadband Router (Cisco cBR) is an Edge Services platform designed for cable MSOs. It supports the RF and Data-over-Cable Service Interface Specifications (DOCSIS) interfaces of a Cable Modem Termination System (CMTS) and digital optical interfaces such as Passive Optical Networks (PON) and point-to-point Ten Gigabit Ethernet.
Product Characteristics
Front Panel
- Eight RF line cards
- Two Supervisor Cards
- One power entry bezel
- Two USB Type A connectors
- One USB mini-Type B (console) port
- LEDs
Note For detailed information on these, see the installation guide at: http://www.cisco.com/c/dam/en/us/td/docs/cable/cbr/Cisco-cBR/IOS-XE-16-5-1/index.html.
Figure 1 Cisco cBR-8 Router Front Panel (Shown as an Example)
Back Panel
- Eight RF PICs
- Two Supervisor PICs
- Six DC Power Modules with redundant input feeds or six AC Power Modules
- Five Fan Modules
- LEDs
- Two Timing ports (one 1 PPS and one 10 MHz)
- One Console port
- One Auxiliary port
- One GPS port
- One CM/DTP port
- Two DTI ports
- Two NME ports
- Eight SFP+ ports
Note For detailed information on these, see the router installation guide at: http://www.cisco.com/c/dam/en/us/td/docs/cable/cbr/Cisco-cBR/IOS-XE-16-5-1/index.html.
Figure 2 Cisco cBR-8 Router Rear Panel with AC FPEM (Shown as an Example)
Figure 3 Cisco cBR-8 Router Rear Panel with DC FPEM (Shown as an Example)
Power System
The Cisco cBR chassis is powered using AC or DC power inputs. The power system consists of the following modules:
The Cisco cBR power system supports:
- Load sharing between the Power Modules
- N+1 redundancy for the DC power systems, and N+1 or 1+1 redundancy for the AC power systems
- Online Insertion and Removal (OIR)
The Cisco cBR-8 Converged Broadband Router (cBR-8) supports:
- One Power Cassette Module: Provides the physical support and keying for the Power Modules. It is keyed with a corresponding FPEM to determine AC or DC support.
- One FPEM: A field replaceable that allows the facility to change from AC to DC power, or vice versa, without replacing the chassis.
- Six Power Modules: Provides the power conversion, filtering, and conditioning from facility input power to the required -52 V midplane power that is used within the chassis. Both AC and DC Power Modules are available depending on the facility input voltage. These modules have internal fans for cooling.
For more information on the power supplies, see the router installation guide on Cisco.com at: http://www.cisco.com/c/dam/en/us/td/docs/cable/cbr/Cisco-cBR/IOS-XE-16-5-1/index.html.
Specifications
For more information on the router specifications, see the router data sheet on Cisco.com at: http://www.cisco.com/c/en/us/products/collateral/video/cbr-8-converged-broadband-router/datasheet-c78-733099.html.
Installing the Router
The Cisco cBR-8 router can be either mounted on the rack at the front or in the middle. Also, the router can be either mounted on a standard 19-inch wide four-post equipment rack unit or a two-post rack unit.
Note The Cisco cBR-8 router usually ships fully loaded. Due to a fully configured system weighing approximately 430 lbs, components must be removed from the chassis to make the chassis lighter for rack installation. Remove all power supplies, supervisor cards, line cards, rear PIC cards and fan modules before rack-mounting to reduce the weight to approximately 117 lbs. For instructions on how to remove the components, see the monitoring sections in the router installation guide.
Before You Begin
To avoid injuring yourself or damaging the equipment, review the Safety Guidelines in Preparing for Installation section in the router installation guide on Cisco.com at: http://www.cisco.com/c/dam/en/us/td/docs/cable/cbr/Cisco-cBR/IOS-XE-16-5-1/index.html.
- Clearance is maintained so that the LEDs on the front panel can be read.
- AC power cord reaches from the AC power outlet to the front-panel connector.
- The router rear panel has a clearance of 11.1 cm.
- Cabling is away from sources of electrical noise, such as radios, power lines, and fluorescent lighting. Make sure the cabling is safely away from other devices that might damage the cables. If needed, allow one RU space between devices to provide room for cabling.
- Airflow around the router and through the vents is unrestricted.
- The temperature around the unit does not exceed the specified operating temperature. If the router is in a closed or multirack assembly, the temperature might be higher than normal room temperature.
- Humidity around the router does not exceed 93 percent.
- Altitude at the installation site is below 4,000 meters.
- For 10/100/1000 fixed ports, cables from the router to connected devices are not longer than 100 meters.
- Cooling mechanisms, such as fans and blowers in the router, can draw dust and other particles causing contaminant buildup inside the chassis, which can result in system malfunction. Install the router in an environment as free as possible from dust and foreign conductive material (such as metal flakes from construction activities).
Installation Warning Statements
Translations of these warning statements appear in the Regulatory Compliance and Safety Information for the Cisco cBR Series Converged Broadband Router at http://www.cisco.com/c/en/us/td/docs/cable/cbr/regulatory/compliance/cbr_rcsi.html .
Rack-Mounting the Router
Rack mount the chassis by securing the rack-mount brackets to two posts or mounting strips in the rack. Use at least four rack-mount screws on each side to fasten the two rack-mount brackets to the rack posts because the rack-mount brackets support the weight of the entire chassis.
You can install the chassis in either a four-post rack unit or a two-post rack unit.
Installing the Power System in the Cisco cBR Chassis
Installing the Power Cassette Module in the Cisco cBR Chassis
The chassis ships with the Power Cassette Module installed. You may need to install the Power Cassette Module to swap the power system of the chassis.
Warning When you install the module, the chassis ground connection must always be made first and disconnected last. Statement 1046
Be aware of the weight and size of the equipment. Handle it with care.
Step 1 Loosen the two screws on the front power entry bezel using a 3/16" flat-blade torque screwdriver. Remove the front power entry bezel from the chassis.
Step 2 Remove the four #6-32 Torx-head screws located on the chassis mounting flanges using a T10 Torx torque screwdriver.
Step 3 Slide the Power Cassette Module into the slot in the chassis until the mounting flanges are fully seated.
Step 4 Insert the four #6-32 Torx-head screws into the mounting flanges. Tighten the screws using a T10 Torx torque screwdriver with a torque of 8-10 in-lb (0.90-1.13Nm) to secure the module.
Step 5 Position the front power entry bezel on the chassis. Insert and tighten the two screws using a 3/16" flat-blade torque screwdriver with a torque of 5-7 in-lb (0.56-0.79 Nm) to secure the bezel.
Installing the FPEM in the Cisco cBR Chassis
The chassis ships with the FPEM installed. You may need to install the FPEM to swap the power system of the chassis. Use this procedure to install the following modules in the chassis:
Install the Power Cassette Module.
Note Attach an ESD-preventive wrist strap to your wrist and connect the other end to the grounding lug connected to the chassis.
Be aware of the weight and size of the equipment. Handle it with care.
Step 1 Remove the four #6-32 Torx-head screws located on the chassis mounting flanges using a T10 Torx torque screwdriver.
Step 2 Carefully slide the FPEM into the slot using the two handles applying even pressure to both the handles until the FPEM is fully seated in the chassis.
Caution To prevent damage to the midplane connectors, do not use excessive force when inserting the FPEM into the slot.
Step 3 Insert the four #6-32 Torx-head screws into the mounting flanges. Tighten the screws using a T10 Torx torque screwdriver with a torque of 8-10 in-lb (0.90-1.13Nm) to secure the module.
Installing the Power Module in the Cisco cBR Chassis
The chassis ships with the Power Module already installed. Use this procedure to install the following modules in the chassis:
Note We recommend that you wire the chassis for 9 KW of power. If you wire it for less than 9 KW power, you may need to add more power modules while adding new hardware or upgrading the existing hardware.
Warning If you are adding new hardware or upgrading the existing hardware, ensure that the power modules installed in the chassis are adequate to support the hardware.
Note Attach an ESD-preventive wrist strap to your wrist and connect the other end to the grounding lug connected to the chassis.
Be aware of the weight and size of the equipment. Handle it with care.
Step 1 Loosen the two screws on the front power entry bezel using a 3/16" flat-blade torque screwdriver. Remove the front power entry bezel from the chassis.
Step 2 Carefully slide Power Module into the bay until it mates with the FPEM connectors.
Note To prevent damage to the FPEM connectors, do not use excessive force when inserting the Power Module into the bay.
Step 3 Move the handle up to lock the Power Module in the chassis.
Step 4 Tighten the screw using a 3/16" flat-blade screwdriver with a torque of 5-7 in-lb (0.56-0.79 Nm) to secure the Power Module.
Step 5 Repeat Step 2 to Step 4 for each Power Module.
Step 6 Position the front power entry bezel on the chassis. Insert and tighten the two screws using a 3/16" flat-blade torque screwdriver with a torque of 5-7 in-lb (0.56-0.79 Nm) to secure the bezel.
Connecting Power to the AC-Powered Cisco cBR Chassis
Note Before connecting AC Power to the AC FPEM, the chassis ground connection must always be made first and disconnected last.
Note Only trained and qualified personnel should be allowed to install, replace, or service this equipment. Statement 1030
The AC FPEM has six input connectors. Each input connector corresponds to the AC Power Module installed in the front of the chassis. They are IEC60320, C22 inlet connectors, which require facility power cords with a C21 style connector. These are similar to a standard C19/C20 combination, but they have chamfers in the upper corners, which are used to distinguish them as rated for 155C instead of the typical 70C used on the C19/C20.
- Attach the Chassis Ground Connection.
- Install the AC Power Cassette Module.
- Install the AC FPIM.
- Install the AC Power Modules.
Step 1 Ensure that the power switch on the AC FPEM is in off (down) position.
Step 2 Connect the AC power cord to the receptacle on the AC FPEM.
Step 3 Tighten the Phillips-head screw on the cable retaining bracket using a #2 Phillips torque screwdriver with a torque of 8-10 in-lb (0.90-1.13Nm).
Step 4 Connect the other end of the AC power cord to the AC source receptacle.
Step 5 Repeat Step 2 to Step 4 for all power connections.
Connecting Power to the DC-Powered Cisco cBR Chassis
Warning The terminal block covers are an integral part of the safety design of the product. Do not operate the unit without the covers installed. Statement 1077
Warning Before connecting DC Power to the DC FPEM, the ground connection must always be made first and disconnected last.
Warning Before performing any of the following procedures, ensure that power is removed from the DC circuit. Statement 1003
Warning Only trained and qualified personnel should be allowed to install, replace, or service this equipment. Statement 1030
The DC FPEM provides terminal blocks for facility input connectivity. It has 12 sets of input terminal blocks to provide each power module with the option of both A and B facility connections.
- Attach the Chassis Ground Connection.
- Install the DC Power Cassette Module.
- Install the DC FPIM.
- Install the DC Power Modules.
The color coding of the DC-input power supply leads depends on the color coding of the DC power source at your site. Typically, green or green/yellow is used for ground (GND), black is used for -48V on negative (-) terminal and red is used for RTN on the positive (+) terminal. Ensure that the lead color coding you choose for the DC-input power supply matches lead color coding used at the DC power source.
For DC input power cables, select the appropriate wire gauge based on the National Electrical Code (NEC) and local codes for 60-amp service at nominal DC input voltage (-48 VDC). Two pairs of cable leads, source DC (-) and source DC return (+) on P-A and P-B, can be used for each DC Power Module. These cables are available from any commercial cable vendor. All input power cables for the chassis must have the same wire gauge.
Note You do not need to connect power to both P-A and P-B feeds for each DC Power Module. The DC Power Modules can operate even with one power input connected.
Each DC input power cable is terminated at the FPEM by a cable lug (included in the accessory kit). The cable lugs must be dual-hole, and have a 90 degree tongue (reference Panduit LCD4-14AF-L). They must be able to fit over 1/4-20 terminal studs on 0.625 in (15.88 mm) centers and have a maximum tongue width of 0.6 inches.
Note DC input power cables must be connected to the FPEM terminal studs in the proper positive (+) and negative (-) polarity. Some DC cable leads are labeled, which is a relatively safe indication of the polarity. However, you must verify the polarity by measuring the voltage between the DC cable leads. When measuring the voltage, the positive (+) lead and the negative (-) lead must always match the (+) and (-) labels on the power distribution unit.
To avoid hazardous conditions, all components in the area where DC input power is accessible must be properly insulated. Therefore, before installing the DC cable lugs, ensure to insulate the lugs according to the manufacturer's instructions.
Caution Before installing the DC cable lugs, insulate the entire 90 degree portion of the lugs where the wire is crimped to avoid hazardous conditions where DC input power is accessible through the terminal block cover of the DC FPEM.
- Insulating sleeving
- Torque wrench
- 7/16" hex socket
- Lugs for the cables
- Cables for positive and negative leads
- Crimping tool
Step 1 Ensure that the power switch on the DC FPEM is in off (down) position.
Step 2 Attach the lug to the lead cable. Carefully crimp the receptacle around the cable using the crimping tool. Insulate the entire 90 degree portion of the lug with shrink sleeving for each lead wire.
Step 3 Remove the terminal block cover on each terminal block by pushing down on the bottom tab then pivoting the bottom out.
Step 4 Loosen the 1/4-20 terminal bolts using a torque wrench and 7/16" hex socket and remove them.
Step 5 Connect the negative lead cable and secure it in place with the 1/4-20 terminal bolts using a torque wrench and 7/16" hex socket with a torque of 45-50 in-lb (5.08-5.65 Nm).
Step 6 Connect the positive lead cable and secure it in place with the 1/4-20 terminal bolts using a torque wrench and 7/16" hex socket with a torque of 45-50 in-lb (5.08-5.65 Nm).
Step 7 Repeat Step 5 and Step 6 for each terminal block connection.
Step 8 Reinstall the terminal block covers by clipping them on the top edge of the terminal block housing and then rotating them down until they snap into place.
Other FRU Modules
For more information on other FRUs, see the router installation guide on Cisco.com at:
http://www.cisco.com/c/dam/en/us/td/docs/cable/cbr/Cisco-cBR/IOS-XE-16-5-1/index.html.
Cisco and the Cisco logo are trademarks or registered trademarks of Cisco and/or its affiliates in the U.S. and other countries. To view a list of Cisco trademarks, go to this URL: www.cisco.com/go/trademarks . Third-party trademarks mentioned are the property of their respective owners. The use of the word partner does not imply a partnership relationship between Cisco and any other company. (1110R)
Any Internet Protocol (IP) addresses and phone numbers used in this document are not intended to be actual addresses and phone numbers. Any examples, command display output, network topology diagrams, and other figures included in the document are shown for illustrative purposes only. Any use of actual IP addresses or phone numbers in illustrative content is unintentional and coincidental.
© 2018 Cisco Systems, Inc. All rights reserved.
Сведения об ограничениях в использовании технического средства с учетом его предназначения для работы в жилых, коммерческих или производственных зонах
Оборудование предназначено для производственной или иной коммерческой деятельности, в зонах без воздействия вредных и опасных производственных факторов. Техническое средство не бытового назначения. Оборудование предназначено для эксплуатации без постоянного присутствия обслуживающего персонала. Оборудование подлежит установке и обслуживанию специалистами, обладающими соответствующей квалификацией, достаточными специальными знаниями и навыками.
В случае обнаружения неисправности технического средства, а также для принятия претензий к качеству оборудования обратитесь в компанию, у которой приобретен данный продукт.
Кроме того информацию о технической поддержке Cisco можно получить на официальном веб-сайте Cisco: http://www.cisco.com/cisco/web/RU/support/index.html
Вы также можете воспользоваться автоматической программой для поиска наиболее подходящего контакта в компании Cisco: http://www.cisco.com/cisco/web/siteassets/contacts/index.html?locale=ru_RU
+7 495 961 13 82 (Москва), (8 800) 700 05 22 (Россия)
Казахстан: 8 800 121 4321 (наберите 8, подождите до 2-го сигнала, затем наберите остальные цифры; наберите PIN 800 721 7549).
При наличии действующего контракта на сервисную поддержку в Службе поддержки Cisco Technical Assistance Center (TAC), обратитесь в службу технической поддержки по телефону:
+7 495 961 13 82 (Москва), (8 800) 700 05 22 (Россия) - меню Технические услуги.
Подробная информация об услугах технической поддержки доступна на сайте: http://www.cisco.com/cisco/web/support/RU/tac_overview.html
http://www.cisco.com/cisco/web/RU/support/index.html
Изготовитель гарантирует соответствие основных технических характеристик оборудования техническим характеристикам, приведенным в этикетке, при соблюдении условий и правил хранения, транспортирования, монтажа и эксплуатации, установленных технической документацией.
Гарантия и сервисная поддержка не распространяются на оборудование в следующих случаях:
- При изменении, модификации, неправильном обращении, уничтожении или повреждении, вызванном следующими причинами: (i) естественными причинами; (ii) воздействием окружающей среды; (iii) отказом принять любые необходимые меры; (iv) небрежным или преднамеренным действием или бездействием; или использованием в целях, отличных от тех, которые определены в применимой документации ; (v) действием или бездействием третьего лица;
- При признаках воздействия огня; воды; химических веществ, включая, но не ограничивая, нанесение краски, покрытие иными веществами; неправильной эксплуатации; самостоятельного ремонта; изменения внутреннего устройства; - при наличии механических повреждений; - при наличии признаков, вызванных попаданием внутрь посторонних предметов, жидкостей, насекомых; - при повреждениях, вызванных несоответствием действующим Техническим Регламентам, Государственным стандартам, НПА по вопросам применения на сети связи общего пользования, и другим применимым официальным требованиям параметров питающих, телекоммуникационных, кабельных сетей и других подобных внешних факторов.
Месяц и год изготовления технического средства.
Год изготовления зашифрован в серийном номере устройства в десятеричной системе исчисления в первых двух цифрах после трехзначного буквенного кода и рассчитывается следующим образом: 2012 году изготовления соответствует цифра 16, 2013 – 17, 2014 – 18, 2015 – 19 и так далее. Неделя изготовления указана в виде двух цифр десятеричной системы следующих после кода года. Первой неделе января соответствует код 01, последней неделе декабря 52 или 53. Информация о дате изготовления наносится на месте производства на само оборудование и/или упаковку.Дополнительная информация:
Ознакомиться более подробно с инструкциями по монтажу на английском языке возможно на официальном web-сайте Cisco: http://www.cisco.com/c/dam/en/us/td/docs/cable/cbr/Cisco-cBR/IOS-XE-16-5-1/index.html.
Ознакомиться более подробно с инструкциями по подготовке к использованию продукта на английском языке возможно на официальном web-сайте Cisco: http://www.cisco.com/c/dam/en/us/td/docs/cable/cbr/Cisco-cBR/IOS-XE-16-5-1/index.html
Дополнительная информация, руководства и правила обращения с продуктом, а также возможность загрузки ПО доступны в разделе Product/Technology Support на официальном web-сайте Cisco: http://www.cisco.com/cisco/web/psa/default.htmlCохраните упаковку и этикетку. В случае, если упаковка утрачена, повреждена или на ней отсутствует информация об Импортере или стране, где изготовлено техническое средство, для получения информации об Импортере обратитесь, пожалуйста, в компанию, у которой приобретено техническое средство. Информация о стране производства (на английском языке) указана на продукте. Также для получения информации о стране производства можно использовать web-приложение Trade Tool на сайте cisco.com (на английском языке, требуется серийный номер устройства и регистрация на сайте cisco.com): http://tools.cisco.com/FinAdm/GCTA/servlet/ControllerServlet?action=QueryForm
Компания Изготовитель оставляет за собой право изменять настоящее настоящий документ без предварительного уведомления.
Наименование и местонахождение уполномоченного изготовителем лица.
Уполномоченное изготовителем лицо на территории стран Таможенного Союза: ООО «Сиско Системс»
Адрес местонахождения: 115054, г. Москва, Космодамианская наб., 52, стр. 1 Телефон: (495) 961-14-10 E-mail: rus-cert@cisco.comCisco и логотип Cisco являются товарными знаками или зарегистрированными товарными знаками корпорации Cisco и/или ее дочерних компаний в США и других странах. Чтобы просмотреть перечень товарных знаков корпорации Cisco, перейдите по следующему URL-адресу: www.cisco.com/go/trademarks . Товарные знаки сторонних организаций, упомянутые в настоящем документе, являются собственностью соответствующих владельцев. Использование слова «партнер» не подразумевает наличия партнерских взаимоотношений между Cisco и любой другой компанией. (1110R)
Республика Беларусь, 220034, Минск, бизнес центр «Виктория Плаза» ул. Платонова, д. 1Б, 3 подъезд, 2 этаж
Тел: +375-17-2691691; Факс: +375-17-2691699
Офис в Республике Казахстан:
Казахстан, 050059, Алматы, бизнес центр “Самал Тауэрс”
Ул. О. Жолдасбекова, 97, блок А2, 14 этаж
Тел.: +7-727-244-2101, Факс +7-727-244-2102
www.cisco.ru